SC(B) 13 Cast Resin Wound Core Dry Type Transformer
- 产品描述
-
Product Overview
Structural Design
• Core: It is made by laminating high-quality grain-oriented cold-rolled silicon steel sheets with 45-degree full-slope multi-step joints. The surface is covered with a resin insulation coating, which features moisture resistance, rust prevention and noise reduction.
• Winding: The coils are wound with copper wires or made by foil winding, reinforced with glass fiber. The epoxy resin without filler is vacuum-dried, degassed and dehumidified and then integrally cast. It has high mechanical strength and strong ability to resist short circuits and withstand impacts.
• Cooling and Protection: It is designed for self-cooling. Longitudinal ventilation ducts are reserved inside the walls of the integrally cast high (low) voltage coils. A forced air cooling device can also be equipped. The enclosure protection level is generally IP00 or IP20, effectively preventing external objects from entering the inside of the transformer.
Performance Characteristics
• Energy-saving and High-efficiency: Technologies for reducing no-load loss and load loss are adopted to significantly reduce energy consumption and improve energy utilization efficiency.
• Safe and Reliable: With a fully enclosed structure and dry insulation materials used inside, there will be no oil leakage problem, greatly improving the safety and reliability of the equipment.
• Easy to Maintain: There is no need to carry out complicated tasks such as oil level monitoring and oil quality testing, reducing the maintenance difficulty and cost.
• Low Noise: The noise level of the product is more than 10 to 15 decibels lower than that of the current standards.
Technical Parameters
• Rated Capacity: Usually ranging from 0.5 KVA to 5000 KVA.
• Insulation Grade: Generally F level or H level, which can ensure safe operation under high load and high temperature environments.
• Short-circuit Impedance: Usually between 4% and 8%.
Technical Parameters
Rated Capacity High Voltage Tap Range Low Voltage Vector Group No-load Loss Load Loss Impedance Voltage Sound Power Level Outline Dimension Gauge (kVA) (kV) (kV) (W) (W) (%) (kg) L W (mm) 30 6
6.3
10
10.5
11±2*2.5
±504 Dyn11
Yyn0135 605 4 250 680 (1060) 450 (850) 400 50 195 845 265 700 (1100) 450 (850) 400 80 265 1160 430 860 (1260) 450 (850) 400 100 290 1330 520 940 (1280) 450 (850) 400 125 340 1560 670 1000 (1300) 450 (850) 400 160 385 1800 805 1050(1300) 710 (1010) 550 200 445 2130 930 1050 (1350 710 (1010) 550 250 515 2330 1070 1110 (1510) 710 (1010) 660 315 635 2940 1160 1120 (1520) 710 (1010) 660 400 705 3370 1440 1160 (1560) 870 (1170) 660 500 835 4130 1595 1160 (1560) 670 (1170) 660 630 965 4970 1740 1250 (1560) 870 (1170) 660 630 935 5050 6 1745 1320 (1720) 870 (1170) 660 800 1090 5890 2095 1370 (1770) 870 (1170) 820 1000 1270 6880 2530 1440 (1840) 670 (1270) 820 1250 1500 8190 2885 1485 (1885) 870 (1170) 820 1600 1760 9940 3670 1650 (2050 1120 (1520) 820 2000 2190 1220 4200 1120 (2100) 1120 (1520) 1270 2500 2590 1590 4780 1120 (2160) 1120 (1520) 1070