Categories
Contact us
Address:
Beizhougua Village, Chang'an Town, GaochengDistrict, Shijiazhuang City, Hebei Province, China
Email:
35KV Oil Immersed Power Transformer
- 产品描述
-
Product Overview
35kV series transformers are with the following characteristics,low loss, low noise, protection against thunder and lightninghigh short-circuit withstand capacity and beautiful appearanceetc. it is made by advanced assembling lines and methodwith qualified and refined accessories. it enjoys four remotefunctions."remote communication remote test,remoteadjustment and remote control". By remote control from acomputer, the power station could be free from supervisionin the office. 35kV series energy saving transformers havepassed the identification Test by State Bureau of Machinerylndustry, and State Power Corporation.
35kV series transformers are mainly used in urban and ruralpower grids and other industrial, mining enterprises,poweltransmission and distribution industry and also agricultureprojects.
The core is processed by advanced vertical cut, horizontalcut, and stacking with stepped lap core and grade 3 seamsit disperses the air distribution, improves flux trend, thus,anddecreases the no-load loss, no-load current and noise
The core uses particular adhesive for the plate, press ringand silicon steel surface; and a range of overall structureand measures are used to increase the mechanical strength
New structure of HV, LV windings and reasonable layoutof oil duct and connecting area increases the capacity ofmechanical strength and short-circuit withstand capacity
The tank is bell type or core-lifting type, and the tank side isas corrugated form, with flowing lines, simplicity and beauty.
Technical Parameters
50-1600/35 Series Three-phase Double-winding Distribution Transformers with Off-circuit Tap Changer
Rated Capacity Voltage Ratio(kv) Vector Group LoSS values for S9 serial transformer loss Values for S10 serial transformer LOss values for S11 serial transformer No-load current Impedance Weight Outline DimenSio (KVA) HV LV No-load Loss Full-load Loss No-load Loss Full-load Loss No-load Loss Full-load Loss (%) (%) Oil weight Total weight L W 50 35
38.5±5%
Or
±2×2.5%0.4 Yyn0
Dynl10.21 1.21 0.19 1.15 0.17 1.15 2 6.5 275 740 1100 1000 100 0.29 2.02 0.26 1.92 0.23 1.92 1.8 350 995 1100 1150 125 0.34 2.03 0.31 2.26 0.27 2.26 1.7 430 1250 1100 1150 160 0.36 2.83 0.32 2.69 0.29 2.69 1.6 450 1405 1160 1150 200 0.43 3.33 0.39 3.16 0.34 3.16 1.5 495 1460 1230 1300 250 0.51 3.96 0.46 3.76 0.41 3.76 1.4 520 1625 1250 1300 315 0.61 4.77 0.55 4.53 0.49 4.53 1.4 590 1915 1400 1320 400 0.73 5.76 0.66 5.47 0.58 5.47 1.3 680 2175 1510 1350 500 0.86 6.93 0.77 6.58 0.69 6.58 1.2 760 2485 1620 1370 630 1.04 8.28 0.94 7.87 0.83 7.78 1.1 830 2950 1750 1390 800 1.23 9.9 1.11 9.41 0.94 9.41 1 880 3370 1900 1420 1000 1.44 12.15 1.3 11.54 1.15 11.54 1 1005 4140 2165 1450 1250 1.76 14.67 1.58 13.94 1.41 13.94 0.9 1160 4700 2230 1500 1600 2.21 17.55 1.91 16.67 1.7 16.67 0.8 1250 5570 2250 1650 630-2500/35 Series Three-phase Double-winding Distribution Transformers with Off-circuit Tap Changer
Rated Capaci t y Vol tag e Ratio (ky) Vect or Grou p Loss values for S9 serial transforme r Loss values for S10 serial transforme r LoSs values for S11 serial transformer No- load Curre nt Impeda nce Teight Outline Dimension Gauge (kVA) HV LV No– load Loss Ful1− load Loss No– load Loss Ful1− load Loss No– load Loss Ful1− load Loss (X) (%) 0/1 weight Total weight L H (mm) 630 35
38.5 ± 5%
Or
±2 ×2 .5X6.3
6.6
10
10.5
11Yd11 1.04 8.28 0.94 7.87 0.83 7.78 1.1 6.5 0.65 2.9 2100 1300 2300 820 800 1.23 9.9 1.11 9.4 0.98 9.4 1 0.7 3.2 2200 1350 2350 820 1000 1.44 12.1 5 1.3 11.54 1.15 11.54 1 0.85 3.5 2350 1450 2400 820 1250 1.76 14.6 7 1.58 13.94 1.41 13.94 0.9 1.01 3.84 2500 1600 2450 1070 1600 2.12 17.5 5 1.91 16.67 1.7 16.67 0.8 1.2 5 2600 1700 2500 1070 2000 2.72 19.3 5 2.45 18.38 2.18 18.38 0.7 1.28 6 2730 1800 2600 1070 2500 3.2 20.7 2.88 19.67 2.56 19.67 0.6 1.4 7 2870 1900 2700 1070
Contact Us
Keywords: